An exergetic performance improvement potential of a modified ejector-enhanced auto-cascade refrigeration cycle

Makaleler > Tam Makale · 2025

Yazarlar: İbrahim KARAÇAYLI, Lütfiye ALTAY, Arif Hepbaşlı

INTERNATIONAL JOURNAL OF EXERGY, SCI Expanded İndekslerine Giren Dergi, Uluslararası, Scopus, 2025, cilt 46, ss 228-243

DOI: 10.1504/IJEX.2025.146045

Özet

<p>This study examines both conventional and advanced exergy analyses of a modified ejector-enhanced auto-cascade refrigeration (MEACR) cycle. Conventional exergy analysis shows that the proposed model significantly improves exergy efficiency compared to similar ejector-enhanced auto-cascade refrigeration cycles in the literature. Advanced exergy analysis reveals that 63.47% of the total exergy destruction is avoidable. When the components of the MEACR cycle are investigated, 56.31% of the exergy destruction is attributed to the endogenous part. The low-temperature cycle (LTC) compressor has the highest avoidable endogenous exergy destruction rate of 12.64 kW with 38.5%.</p>