Evaluation of the Suitability of Some Local Materials as Cooling Pads
Makaleler > Tam Makale · 2007
Yazarlar: Tuncay GÜNHAN, Vedat DEMİR, ABDULKADİR YAĞCIOĞLU
BIOSYSTEMS ENGINEERING, SCI Expanded İndekslerine Giren Dergi, Uluslararası, Wos, 2007, cilt 3, ss 369-377
DOI: doi:10.1016/j.biosystemseng.2006.12.001
Özet
<p><span style="color: rgb(33, 37, 41); background-color: rgb(255, 255, 255);">The objective of this study was to evaluate the suitability of pumice stones, volcanic tuff and greenhouse shading net as alternative pad materials to the widely used and commercial one called CELdek. For this purpose, the tests were carried out at four levels of air velocity (0-6, 1-0, 1.3 and 1.6 ms(-1)) four levels of water flow rate (1.0, 1-25, 1.5 and 1.75 l min(-1)) and three levels of pad thickness (50, 100 and 150 mm). The tests were made at 30 +/- 1 degrees C and 40 +/- 1% relative humidity air conditions. The temperature of water flow was kept constant at 25 +/- 2 degrees C during the tests. According to the results of this study, it can be stated that the volcanic tuff pads are good alternatives to the CELdek pads at 0.6 m s(-1) air velocity. </span></p>