EXPERIMENTAL ASSESMENT OF REFRIGERATION SYSTEM CHARACTERISTICS WITH SCROLL COMPRESSOR

Articles > Article ยท 2013

Authors: Orhan EKREN, Serhan Kucuka

ISI BILIMI VE TEKNIGI DERGISI-JOURNAL OF THERMAL SCIENCE AND TECHNOLOGY, Journal Indexed in SCI Expanded, International, 2013, vol 33, pp 119-124

Summary

In this study, characteristics of a chiller system are investigated. The experimental setup consist of an air cooled condenser, a liquid type shell-tube evaporator, and a scroll compressor. Compressor speed is changed between 30-60 Hz via PWM type frequency inverter. Mass flow rate of the refrigerant R134a is controlled by an electronic expansion valve (EEV) and a thermostatic expansion valve (TXV) in the system. The cooling capacity of the chiller system is about 3 kW. For determining the performance characteristics of the system eight parameters are considered. These are the EEV opening, superheating, subcooling, evaporation/condensing temperatures, and refrigerant flow rate. It is found that the COP decreased to its half and cooling capacity increased 37% by increasing the frequency from 30 Hz to 60 Hz. According to analysis, superheating changing affects various parameters in the system and also it is important to monitor this parameters.

View details